The G 180 mobile generator provides all the power needed for larger applications. The durable sound-attenuated generator is an excellent choice for larger applications where quiet mobile, prime power is needed. Used for construction, commercial, industrial, special event and emergency management applications. The T4i model is especially suited for areas requiring BAT (Best Available Technology) to meet the most stringent EPA, CARB air standards. A digital controller monitors and protects the generator and engine while providing continuous operating data on an easy to read LCD display. Large fuel tank provides convenient, long run times.
G180 | ||||
---|---|---|---|---|
Dimensions |
||||
L x W x H Operating (Skid) in | 132 x 52 x 68 | |||
L x W x H Shipping (Skid) in | 135.5 x 54.5 x 81.5 | |||
L x W x H Shipping/Operating (Trailer) in | 199 x 84.5 x 99 | |||
Weights |
||||
Weight Dry (Skid) lb | 6,213 | |||
Weight Operating (Skid) lb | 8,313 | |||
Weight Shipping (Skid) lb | 6,580 | |||
Weight Operating (Trailer) lb | 9,793 | |||
Weight Shipping (Trailer) lb | 7,693 | |||
Operating data |
||||
Trailer coupling Type | Pintle | |||
Standby output kW | 157 | |||
Prime output kW | 143 | |||
Voltage 3 Phase V | 240/480 | |||
Current 3 Phase (Prime) A | 240/480 | |||
Current 1 Phase (Prime) A | 120/240 | |||
Voltage 3 Phase V | 208, 220, 240, 416, 440, 480 | |||
Voltage 1 Phase V | 120, 127, 139, 240, 254, 277 | |||
Circuit breaker (Main) A | 500 | |||
Frequency Hz | 60 | |||
Power factor 1 Phase cos Φ 1~ | 1 | |||
Power factor 3 Phase cos Φ 3~ | 0.8 | |||
Sound level (LwA) at Prime (23 ft / 7 m) dB(A) | 69.9 | |||
Receptacles -20 Amp GFI Duplex | 2 | |||
Receptacles -50 Amp Twist Lock | 3 | |||
Engine / Motor |
||||
Engine / Motor | Liquid-Cooled, 6 Cylinders | |||
Engine / Motor manufacturer | John Deere | |||
Emissions Certified | Tier 3 | |||
Displacement in³ | 415 | |||
Operating performance ISO 3046hp | ||||
Operating performance SAE J1995, ISO 8528-1 hp | 237 | |||
at rpm rpm | 1,800 | |||
Coolant Capacity US qt | 30.4 | |||
Engine oil Capacity US qt | 34.3 | |||
Fuel type | Diesel | |||
Fuel consumption (Prime Load)US gal/h | 10.8 | |||
Tank capacity -Fuel US gal | 291.7 | |||
Quantity (Battery) | 1 | |||
Battery V | 12 | |||
Generator model | Mecc Alte, Brushless w/AVR | |||
Voltage control No Load to Full Load +/- % | 1 | |||
Voltage control Steady State +/-% | 0.2 | |||
Generator insulation (class) | H | |||
Frequency (Generator Speed) Hz | 60 | |||
Runtime at 100% Prime Load h | 25 | |||
Runtime at 75% Prime Load h | 32.2 | |||
Runtime at 50% Prime Load h | 44 | |||
Runtime at 25% Prime Load h | 86.1 | |||
DEF Type | ||||
DEF Consumption US gal/h | ||||
DEF Tank Capacity US gal | ||||
Runtime DEF 100% Prime Loadh |